NirouTrans Company

Cast resin voltage transformers (Up to 36kV)


These transformers are used to separate measuring and protection equipment from high voltage circuits and to transform the voltage to the values required by the measuring and protection equipment.

Indoor Installation

Indoor Cast resin inductive transformers Niroutrans
These transformers can be installed in medium voltage coupling panels, incoming and outgoing feeder in a substation.
The main insulation of these instrument transformers is epoxy resin compound cast in high vacuum, with superior dielectric and mechanical properties. Depending on the required specification, one of the models, 4VPA1, 4VPA, GUPT, TIPT can be used.




4VPA1

4VPA1


Voltage:
12, 24 and 36 kV

Voltage factor:
1.2 cont. 1.9/30 s

Single Pole

Read more

GUPT

GUPT


Voltage:
12, 24 and 36 kV

Voltage factor:
1.2 cont. 1.9/30 s

Single Pole
TIPT

TIPT


Voltage:
12, 24 and 36 kV

Voltage factor:
1.2 cont. 1.9/30 s

Single Pole
4VPA

4VPA


Voltage:
12, 24 and 36 kV

Voltage factor:
1.2 cont. 1.9/30 s

Double Pole

Read more


Outdoor Installation

Outdoor Cast resin inductive transformers Niroutrans
The main insulation of these of these instrument transformers is epoxy resin compound based on sylco alphatic resin cast and it can keep the insulation properties under different climatic conditions. VPV1 and VPV models are available for different applications.






VPV1

VPV1


Voltage:
12, 24 and 36 kV

Creepage distance:
up to 1164 mm

Voltage factor:
1.2/cont.

Single Pole

Read more

VPV

VPV


Voltage:
12 and 24 kV

Creepage distance:
660 mm

Voltage factor:
1.2/cont.

Double Pole

Read more

downloadDownload instruction for installation and maintenance
downloadDownload instruction for installation and maintenance (Gun PT)


Details
Unit
MV-Voltage Transformer(Type: 4VPA1, 4VPA, VPV1, VPV, GUPT, TIP)
Highest System Voltage
Um (kV)
12
24
36
Insulation level
BIL (kV)
28-75
50-125
70-170
Rated Primary Voltage
Un (kV)
11 , 11/√3
20 , 20/√3
33 , 33/√3
Rated Secondary Voltage
Usn (V)
100/√3 or 110/√3 or 100 or 110 or 100/3
Rated Secondary Burden
VA
Up to 100
Number of secondary Windings
Up to 3
Class
3P , 0.2 , 0.5
Rated Frequency
F (Hz)
50/60
Installation
Indoor / Outdoor