Generator Circuit Breakers

Generator Circuit Breakers Niroutrans
The Generator Circuit-Breaker System type HEC 3 is produced in Nirou Trans Company under license of ABB Switzerland.
HEC Generator Circuit-Breaker System has been developed as a system suitable for application in all types of power plants. It is also suitable for retrofitting existing power plants, when these are modernized, extended and/or automated.
It is available for both indoor and outdoor application. Generator circuit-breakers are connected between a generator and the step-up voltage transformer.
They are generally used at the outlet of high power generators in order to protect them in a reliable, fast and economic manner.


Some advantages of Generator Circuit-Breakers are as follows:

1- Simplification of operation Procedures.
2- Improved protection of the generator and the main and unit transformers.
3- Increased Safety
4- Higher power plant availability

The schematic diagram of a GCB is as follows:
Generator Circuit Breakers Map Niroutrans

Technical data and dimensions
Generator circuit-breaker system type

1- Generator circuit-breaker
2- Disconnector
3-4 Earthing switches
5- Starting switch for gas turbines
7- Braking switch or manual
9-12 Voltage transformers
13-14 Current transformers
15- Surge arrester
16-17 Surge capacitors
19- System enclosure
20- Earthing link

General Type Extra Detail HEC 3 Unit
Rated maximum voltage 25.3 kV
Rated frequency 50/60 Hz
Rated continuous current 50 Hz 12 kA,rms
Rated continuous current 60 Hz 11.5 kA,rms
Rated insulation level
Rated power frequency withstand voltage
To erath and across circuit-breaker/switch contacts 60 kV,rms
Across isolating distance of disconnector 70 kV,rms
Rated lightning impulse withstand voltage
To earth and across circuit-breaker/switch contacts *) 125 kV,peak
Across isolating distance of disconnector 145 kV,peak
Circuit-Breaker
Rated peak withstand current 300 kA,peak
Rated short-time withstand current 100 kA,3s
Rated short-circuit making current 300 kA,peak
Rated short-circuit breaking current 100 kA,rms
Rated operating sequence co-30min-co
Rated interrupting time Disconnector 53 ms
Rated peak withstand current 300 kA,peak
Rated short-time withstand current 100 kA,3s
Operating time 2 s
Earthing Switch
Rated peak withstand current 300 kA,peak
Rated short-time withstand current 100 kA,1s
Operating time 2 s
*) On request BIL= 150 kV peak possible